ANSWER
-
If your sensor is missing production counts, the most likely cause is that the sensor's detection distance has been configured too short. As a result, some products may not enter the detection area and will not be counted.
You may need to retrain the sensor following this approach:
- Remove all objects from in front of the sensor.
- Press the TEACH button quickly (between 25 ms and 1 second).
- Place an object at the position where products will normally pass through the sensor.
- Press the TEACH button quickly again.
- Wait for the sensor to display Success.
After teaching is complete:
- The sensor automatically sets the detection threshold between the background and the detected object.
- If no object is detected during one of the teaching steps, the sensor automatically uses the maximum detection distance (150 mm for HL150 or 500 mm for HL500) as the teaching point.
- This is the default and recommended teaching method for most production counting applications.
- If you have done this and are still experiencing issues, we recommend sending us a recording showing what your setup looks like along with product/items passing through the sensor.
ADDITIONAL DETAILS
- An orange sensor light remaining on while a product is in front of the sensor is expected behavior. The sensor only registers a single count for each detection event, regardless of how long the product remains in front of it.
- If products are consistently being missed, the sensor may need to be taught again using a shorter detection distance. A common recommendation is to teach the sensor using a hand or similar object positioned around the middle of the conveyor, rather than using the product itself. This helps ensure all products enter the sensor's detection zone.
- For more information, feel free to look at Omron's sensor guide here
LIMITATIONS (if applicable)
- An orange sensor light does not indicate multiple counts or a sensor fault.
- An incorrect sensor teaching distance can result in missed counts.
- This guidance assumes the hardware is functioning correctly and the issue is related to the sensor configuration.