Troubleshooting: Missing Data / Factbird DUO Offline

Summary: Use this guide to troubleshoot your Factbird DUO if it shows “Missing Data,” displays a red dotted line at 0 pcs/min, or appears offline. This resolves connectivity, power, and communication issues.

 

Symptom

You may be experiencing this issue if:
  • The production graph shows a red dotted line

  • Hover text says “Missing Data”

  • No production data is received

  • DUO status LED is blinking red

  • Device is not connecting to Wi-Fi or cellular

Screenshot 2026-03-02 124115.png

Prerequisites

Before you begin, please confirm:
  • You have physical access to the DUO

  • You can access the device page in Factbird


Diagnostic Steps

Follow these steps in order.
  1. Verify Power Supply

    1. What to check: Confirm power cable is secure (firmly connected to both the DUO and the outlet) and LEDs are active (not completely off).

    2. What result indicates success: LEDs are on and stable.

    3. If result is not correct: Try a different outlet or power supply. If still no power, contact Support.

  2. Check Physical Placement

    1. What to check: Ensure DUO is not inside a metal cabinet or high-interference enclosure.

    2. What result indicates success: Device is installed in an open area.

    3. If result is not correct: Relocate (permanently) and power cycle. If still offline, go to Step 3.

  3. Power Cycle the Device

    1. What to check: Disconnect power for 10 seconds and then reconnect.

    2. What result indicates success: Device reconnects and data resumes.

    3. If result is not correct, go to Step 4.

  4. Verify Network Connectivity 

    1. What to check: Confirm whether the DUO is configured for cellular or Wi-Fi.

      1. (Wi-Fi): If using Wi-Fi, verify correct SSID and password were entered.  If incorrect Wi-Fi credentials were entered, wait for the DUO to come online via cellular and remove the incorrect Wi-Fi setup.  If it does not reconnect via cellular, manually reset Wi-Fi credentials.

      2. (Cellular): If using cellular, switch to Wi-Fi for a stronger connection.

    2. What result indicates success: Device appears online in Factbird.

    3. If result is not correct: Go to Step 5.

  5. Check Network Firewall

    1. What to check: Ensure required Factbird endpoints are properly whitelisted according to Network Firewall Requirements.

    2. What result indicates success: Outbound connections required by Factbird are allowed.

    3. If result is not correct: Update firewall rules and power cycle. If still offline, go to Step 6.

  6. Verify Firmware Version

    1. What to check: Confirm firmware is up to date on device page (a purple update button indicates there is an update available).

    2. What result indicates success: Device runs latest firmware.

    3. If result is not correct: Initiate update. If update fails or device remains offline, contact Support.


Common Root Causes

  • Cause 1: No or unstable power
    • Loose cable, faulty power supply, or unstable outlet.

    • Resolution: Secure or replace power supply, use a different outlet, ensure secure connection.

  • Cause 2: Signal interference

    • Device installed inside metal cabinet or other high-interference area.

    • Resolution: Relocate device and power cycle.

  •  Cause 3: Poor cellular signal

    • Device is running on the cellular network only

    • Resolution: Connect device to Wi-Fi and power cycle

  • Cause 4: Incorrect Wi-Fi credentials

    • Wrong SSID or password prevents connection.

    • Resolution: Remove incorrect Wi-Fi setup (by pressing the bin icon button or manually removing the Wi-Fi from the device), power cycle, and reconfigure.

  • Cause 5: Network firewall blocking traffic

    • Required endpoints not whitelisted.

    • Resolution: Update firewall configuration per Network Firewall Requirements.

  • Cause 6: Outdated firmware

    • Device not running latest firmware.

    • Resolution: Update to latest firmware version.


Resolution

Once resolved:
  • The status LED indicates normal operation

  • DUO appears online in the Factbird system

  • Red dotted line disappears

  • Live production data resumes


If The Issue Persists

Contact Support and include:
  • Device ID

  • Current firmware version

  • LED status description

  • Network type (Cellular or WiFi)

  • Steps already performed