Summary: Use this guide to troubleshoot your Factbird DUO if the device is online but production remains at 0 pcs/min while the line is running. This resolves sensor wiring, configuration, and input detection issues.
Symptom
You may be experiencing this issue if:
The production graph shows a solid blue line at 0 pcs/min
Hovering over the graph shows numeric zero production values
The DUO input LED does not blink when products pass
No counts appear while production is running
Prerequisites
Before you begin, please confirm:
The DUO is powered on
The sensor is physically installed and connected
Products are passing the sensor
Diagnostic Steps
Follow these steps in order:
-
Verify DUO input configuration (NPN/PNP)
What to check: Confirm the configured sensor type matches the physical sensor specification.
What result indicates success: Configuration matches the sensor type.
If result is not correct, update configuration and retest. If still not counting, go to Step 2.
-
Confirm Correct Physical Input (Port/Channel)
What to check: Observe which DUO LED blinks when product passes.
What result indicates success: Configured port/channel LED blinks.
-
If result is not correct: Correct wiring or update configuration. If still not counting, go to Step 3.
-
Verify sensor power
What to check: Confirm the sensor has power (indicator LED or display).
What result indicates success: Sensor shows power and activates when product passes.
If result is not correct, inspect wiring and restore power. If still not counting, go to Step 4.
-
Test with a known working sensor
What to check: Replace current sensor with a verified working sensor.
What result indicates success: DUO counts when product passes.
If result is not correct, escalate to Support.
Common Root Causes
-
Cause 1: Incorrect NPN/PNP configuration
Configuration does not match sensor type.
Resolution: Update configuration.
-
Cause 2: Sensor not powered or faulty
Sensor does not output signal.
Resolution: Restore power or replace sensor.
-
Cause 3: Wiring to wrong input port
Signal connected to incorrect channel.
Resolution: Correct wiring or update configuration.
Resolution
Once resolved:
DUO input LED blinks when products pass
Counts appear immediately in Factbird
Production graph reflects actual output
If The Issue Persists
Contact Support and include:
DUO serial number
Photos of wiring and sensor model
Screenshot of DUO input configuration
Confirmation of sensor power status